- Scanners[2]
- Connectors[9]
- Other Electrical Equipment[7]
- AC/DC Adapters[1]
- Industrial Power Supply[7]
- Switching Power Supply[10]
- Uninterrupted Power Supply (UPS)[10]
- DIP Switches[8]
- Other Switches[1]
- Rocker Switches[10]
- Slide Switches[1]
- Filters[4]
- Sensors[2]
- Other Electronic Components[7]
- Printing Machinery[2]
- Other Analysis Instruments[3]
- Clamp Meters[10]
- Power Meters[10]
- Voltage Meters[2]
- Temperature Instruments[2]
- Other Store & Supermarket Equipment[5]
- Contact Person : Ms. Li Lisa
- Company Name : Besternasia Electronics Limited
- Tel : 86-755-86372529
- Fax : 86-755-86652135
- Address : Guangdong,Shenzhen,Room 402, Floor 4, Building 2, Zhongxing Industry Town, Chuangye Road, Nanshan District, Shenzhen
- Country/Region : China
- Zip : 518000
Related Product Searches:1-phase QUINT POWER power supply-2866747 QUINT-PS/ 1AC/24DC/ 3.5,High Quality,2866747 QUINT-PS/ 1AC/24DC/ 3.5, switching power supply,2866747 QUINT-PS/ 1AC/24DC/ 3.5
Input data
Nominal input voltage | 100 V AC ... 240 V AC |
AC input voltage range | 85 V AC ... 264 V AC |
DC input voltage range | 90 V DC ... 350 V DC |
Short-term input voltage | 300 V AC |
AC frequency range | 45 Hz ... 65 Hz |
DC frequency range | 0 Hz |
Current consumption | Approx. 1.4 A (120 V AC) |
Approx. 0.8 A (230 V AC) | |
Inrush surge current | < 20 A (typical) |
Power failure bypass | > 20 ms (120 V AC) |
> 80 ms (230 V AC) | |
Input fuse | 5 A (slow-blow, internal) |
Permissible backup fuse | B6 |
B10 | |
B16 | |
Additional text | AC: 1 x circuit breaker - recommended fuse |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor |
Output data
Nominal output voltage | 24 V DC ±1% |
Setting range of the output voltage | 18 V DC ... 29.5 V DC (> 24 V constant capacity) |
Output current | 3.5 A (-25°C ... 60°C, UOUT = 24 V DC) |
4 A (with POWER BOOST, -25°C ... 40°C permanently, UOUT = 24 V DC) | |
15 A (SFB technology, 12 ms) | |
4 A (UIn ≥ 100 V AC) | |
Derating | 60 °C ... 70 °C (2.5%/K) |
Connection in parallel | Yes, for redundancy and increased capacity |
Connection in series | Yes |
Control deviation | < 1 % (change in load, static 10% ... 90%) |
< 2 % (change in load, dynamic 10% ... 90%) | |
< 0.1 % (change in input voltage ±10%) | |
Residual ripple | < 50 mVPP (with nominal values) |
Maximum power dissipation idling | 3.5 W |
Power loss nominal load max. | 11 W |
Width | 32 mm |
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
35 mm | |
Net weight | 0.5 kg |
Operating voltage display | Green LED |
Efficiency | > 88 % (for 230 V AC and nominal values) |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Degree of protection | IP20 |
Protection class | I |
MTBF (IEC 61709, SN 29500) | > 500000 h |
Ambient temperature (operation) | -25 °C ... 70 °C (> 60 °C derating) |
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, no condensation) |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | Can be aligned: 5 mm horizontally, 15 mm next to active components, 5 cm vertically |
Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
Noise immunity | EN 61000-6-2:2005 |
Low Voltage Directive | Conformance with LV directive 2006/95/EC |
Standard – Electrical equipment of machines | EN 60204 |
Standard - Safety of transformers | IEC 61558-2-17 |
Standard - Electrical safety | IEC 60950-1/VDE 0805 (SELV) |
Shipbuilding approval | Germanischer Lloyd (EMC 2), ABS, LR, RINA, NK, BV |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations | EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage | IEC 60950-1 (SELV) and EN 60204 (PELV) |
Standard - Safe isolation | DIN VDE 0100-410 |
DIN VDE 0106-1010 | |
Standard – Protection against electric shock | DIN 57100-410 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment | DIN VDE 0106-101 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Standard – Equipment safety | GS (tested safety) |
Standard - Approval for medical use | IEC 60601 |
Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47-0706 Compliance Certificate |
Certificate | CB Scheme |
UL approvals | UL Listed UL 508 |
UL/C-UL Recognized UL 60950 | |
UL listed ANSI/ISA-12.12.01 class I, division 2, groups A, B, C, D | |
DeviceNet approval | DeviceNet™ Power Supply Conformance Tested |
1-phase QUINT POWER power supply-2866747 QUINT-PS/ 1AC/24DC/ 3.5