Inform PDS 500 UPS (Pyramid EX Series)

Inform PDS 500 UPS (Pyramid EX Series)
Product Detailed
1. Authorized Distributor in CHINA 2. True on-line double conversion technology 3. Full front access 4. IGBT & PWM Technolo

 PYRAMID EX SERIES Uninterruptible Power Systems True On-Line Technology 3 Phase in 3 Phase out ( 500 to 1000 kVA )

True on-line double conversion technology with high efficiency State of the art IGBT & PWM Technology Built - in maintenance & Automatic by-pass Evolution and redundancy guaranteed by Parallel Systems ( up to 4 units ) User Friendly LCD Panel helps to feature the ups easily. Full front access to whole internal components reduces the repair&maintenance time. Expandable and variable battery blocks Communication Interface and Monitoring Software 12 pulse rectifier option
MODELPDS 500 PDS 600 PDS 800 PDS 1000
Output Power (kVA)5006008001000
Output Power (kW)400480640800
INPUT 
Voltage380V / 400V / 415V 3 Phase+Neutral+PE
Tolerance± 15%
Frequency50 - 60 Hz
Tolerance± 10%
DC Ripple Voltage± 1%
DC Ripple Currentmax 2% of battery capacity defined in Amps
OUTPUT 
Power Factor0.8
Voltage380V / 400V / 415V 3 Phase+Neutral+PE
Tolerance static conditionstep load (0%-100%-0%)step load (0%-50%-0%) ±1%±8% recovering within tolerance into 2 cycles±3% recovering within tolerance into 2 cycles
Total Harmonic Distortion< 2% (@ 100% linear load)
Crest Factor3:1 with 80% load
Frequency50 or 60 Hz.
Frequency tolerance (free running)± 0.01%
Frequency tolerance (synchronized with utility)±5%
Overload125% load150% load 10 min1 min
Overall Efficiency0.925
Output Neutral Rating2
BATTERY 
TypeMaintenance-free lead acid batteries
Quantity32 pcs 12V Blocks
Nominal DC Voltage384VDC
Float Voltage at 20C436VDC
Automatic and Manual Battery TestStandard
STATIC BYPASS 
Input ConfigurationCommon with Rectifier or Seperate
Transfer Limits± 10% of Nominal Adjusted Output Voltage
Overload CapabilityContinous at 110%
Short Circuit Capability5min @ 200% and half cycle @ 1000% (non repetitive)
ENVIRONMENT 
Audible Noise<68dBA<70dBA
Operating Temperature0-40°C
Relative Humidity (non condensing)0-95%
Protection ClassIP 20
PHYSICAL SPECIFICATIONS 

Weight Without Battery (kg)

2900310038004000
Dimensions (mm) WxDxH3400*1000*18003400*1400*18004200*1400*1800
STANDARDS 
 EN 62040-1-1 (safety), EN 62040-2(EMC), EN 62040-3 (VFI-SS-111)