Inform SD3110 On line UPS

Inform SD3110 On line UPS
Product Detailed
1. Authorized Distributor in CHINA 2. Increased Power Factor Correction PFC 3. RS 232 and relay interface 4. SNMP support

SAVER PLUS DSP SERIES Uninterruptible Power SystemsOn-Line “Double Conversion” Technology3 phase in-1 phase out, 10 to 20 kVA On-line ‘double conversion’ technology Real Digital Signal Processor (DSP) controlled, IGBT technology Wide input voltage range (140V-480V) Increased Power Factor PFC (>0.97) Intelligent Battery Management System extends the life time of batteries Transformerless Design Small Dimensions Artificial intelligence algorithms to improve reliability and technical performance Manual Bypass LCD display RS 232 and relay interface Management and monitoring software available for all operating systems and SNMP support

TYPESD3110SD3115SD3120
Power (kVA)101520
INPUT 
Nominal Voltage380V / 400V / 415V 3Phase, N
Minumum Voltage140V  3Phase, N
Minumum Voltage (at full load)260V  3Phase, N
Maximum Voltage480V  3Phase, N
Frequency50 - 60Hz (45 to 65 Hz)
Nominal Current11.8 A / phase17.4 A / phase23.3 A / phase
Maximum Current36 A peak / phase53 A peak /phase71 A peak / phase
Power Factor>0,97
OUTPUT 
Power Factor0.7
Nominal Voltage220 /230V (adjustable)
Wave FormSinus
Total Harmonic Distortion< 3%
Frequency50Hz or 60Hz (adjustable)
Voltage Regulation (Static)1%
Crest Factor3
Overload>30s (at 150 % load)
Total Efficiency>91%
BATTERY 
TypeMaintenance-free lead acid batteries
Quantity (pcs)2032
Recharging Time< 4 h
Discharge Current Wave< 10%
DISPLAY 
LED PanelLine, Bypass, Battery, Inverter, Overload, Fault Indicators
LCD PanelLoad%, Battery Temperature, Input&Output&Battery Voltages, Output Frequency
STATIC BYPASS 
Voltage Tolerance10% (adjustable)
Frequency Tolerance3Hz (adjustable)
Transfer Time0 ms
PROTECTION 
ProtectionsOverload Protection, Short Circuit Protection, High Temperature, Over Voltage, Over Current

COMMUNICATION INTERFACE  
Interface (Communication Ports)RS 232
Dry Contact SignalsUps shutdown, mains failure, low battery, by-pass active, summary alarm
ENVIRONMENT 
Temperature0 - 40°C
Suggested Temp. to extend battery life20 - 25°C
Humidity< 95%
Acoustic Noise<55dB from 1m distance
Protection ClassIP 20
PHYSICAL SPECIFICATIONS  
Net Weight (without battery)55kg125kg130kg
Dimensions (mm) (WxDxH)270x730x780430x820x970
STANDARDS 
 EN 62040-1-1 (safety), EN 62040-2 (EMC)

Inform SD3110 On line UPS



Copyright Notice @ 2008-2022 ECVERY Limited and/or its subsidiaries and licensors. All rights reserved.